Long Service Life - Thick plate design and efficient gas recombination yield a service life expectancy of up to 10 years in
standby mode.
Low Internal Resistance - Superb high-rate discharge characteristics ensure reliable performance in UPS and Telecom
applications.
Maintenance-Free, Non-Spillable - Proven VRLA technology guarantees safe operation without maintenance and ‘nonrestricted
article’ status for transportation.
Handles - Integral carrying handles.
Low Self-Discharge - Lead-calcium alloy grids and use of high purity lead account for superior shelf-life characteristics permitting storage for extended periods of time.
Designed-In Reliability - Cutting-edge manufacturing and process control combined with meticulous quality assurance
procedures guarantee consistent and dependable performance.
Nominal Voltage ........................................................................ 12 volts (6 cells)
Nominal Capacity
20-hr. (8.30A to 10.80 volts) ........................................................ 166.0 AH
10-hr. (15.3A to 10.80 volts) ........................................................ 153.0 AH
8-hr. (18.3A to 10.50 volts) .......................................................... 146.4 AH
5-hr. (26.30A to 10.50 volts) ..................................................... 131.5 AH
3-hr. (39.80A to 10.50 volts) .......................................................119.4 AH
1-hr. (91.8A to 9.60 volts) ............................................................. 91.8 AH
Approximate Weight ............................................................ 103 lbs. (46.7 kg)
Energy Density (10-hr. rate) .................................. 1.51 W-h/in3 (91.87 W-h/l)
Specifi c Energy (10-hr. rate) .............................. 17.83 W-h/lb (39.30 W-h/kg)
Internal Resistance (approx.) ..................................................... 4.0 milliohms
Max Short-Duration Discharge Current (10 Sec.) ................... 900 amperes
Shelf Life (% of nominal capacity at 68°F (20°C))
1 Month ...................................................................................................... 97%
3 Months ..................................................................................................... 91%
6 Months .................................................................................................... 83%
Operating Temperature Range
Charge .. ........................................................... -4°F (-20°C) to 122°F (50°C)
Discharge ....................................................... -40°F (-40°C) to 140°F (60°C)
Case ........................................................ ABS Plastic (UL94 V-O flame retardant)
Dimensions: L: 485 W: 170 H: 242 HT: 224 (mm)
Cycle Applications: Limit initial current to 25.0A. Charge until battery voltage (under charge) reaches 14.4 to 14.7 volts at 68°F (20°C). Hold at 14.4 to 14.7 volts until current drops to under 1.53A. Battery is fully charged under these conditions, and charger should be disconnected or switched to “float” voltage. “Float” or “Stand-By” Service: Hold battery across constant voltage source of 13.5 to 13.8 volts continuously. When held at this voltage, the battery will seek its own current level and maintain itself in a fully charged condition.
Note: Due to the self-discharge characteristics of this type of battery, it is imperative that they be charged within 6 months of storage, otherwise permanent loss of capacity might occur as a result of sulfation.